Metacaulk Mortar
Product Details
Metacaulk Fire Rated Mortar fire and smoke barrier mortar, tested to ASTM E 814 (UL1479). It is a fire-rated gypsum and cement mortar that sets quickly and is easy to use. When mixed with water to the proper consistency, it becomes a high-strength fire-rated mortar that effectively resists flames, gases and toxic smoke, providing excellent protection against the spread of fire and smoke in the event of a fire.
Size
Red, 20 kg.
Testing Data
- For specific test criteria, refer to the UL Product iQ and Interek Directory of Building Products https://iq.ulprospector.com/en
- Metacaulk FRM Fire Rated Mortar was tested at positive pressure with a minimum 0.01 (2.5 Pa) inches water and in accordance with ASTM E814 (UL 1479).
- Tested to the time-temperature requirements of ASTM E119 (UL 263).
- Tested to standards of CAN/ULC S115, S101 and S102.

Interested in this product? Contact our team for pricing or installation advice.
Features
Metacaulk Fire Rated Mortar Fire-rated mortar for filling large openings. It acts as insulation to seal through-openings and penetrations in fire-rated walls and floors, and shafts. It can be used with electrical cables, communication cables, aluminium or steel cable trays, around metal pipes (steel, copper, etc.) and in blank openings.
- Fire tested for up to 4 hours, UL 1479 / ASTM E 814
- Through-penetration firestop tested to the time-temperature requirements of UL 263 / ASTM E119
- Red colour for easy inspection (prevents mix-ups with other mortars)
- Easy to adjust consistency, non-sagging (pourable or trowelable)
- Can be easily cut, drilled or resealed if future modifications are required
- Contains a biocide that resists fungal growth
- Contains no asbestos
- Safe and easy to use; no special tools are needed for mixing or installation
- UL Certificate Number: R14546 – Fill, Void or Cavity Materials
Instructions for Use
Mixing procedure: mix with clean water in a suitable container. Gradually add the dry mortar mix to the water while mixing. Stir by hand or with an electric mixer
to ensure the mixture is smooth and free of lumps.
Recommended mixing ratio: mortar mix : water (by volume)
Pourable for floor openings: 2 1/2 : 1
Stiff for wall openings: 3 : 1
Recommendation
Sealing openings requires a suitable backing material, such as mineral wool, installed before pouring the mortar. The boards must be cut to fit the opening so as to avoid leakage.
The product provides fire and smoke resistance for the rated periods specified when installed correctly in accordance with the test results in the “UL Listed” directory.
Technical Data
Curing Times
Workable pot life: Aproximately 45 minutes
Set Hard: 3 to 4 hours (at 77˚F/25˚C)
Fully Cured: 28 Days
Application Temperature: 40˚F – 120˚F
between 4˚C – 49˚C
Contact Us / Request a Quote
Product enquiries, quotations or a site survey
329 Moo 3, Ban Mai, Pak Kret, Nonthaburi 11120, Thailand · View map